Installation and Programming Manual
55
ZONES: CROSS ZONES
Quick Key Item Default Explanation
2 7
CROSS ZONES
Not for UL Installations
no
cross
zoning
§ for additional immunity to false alarms, two related
zones may be linked together so that both must be
violated within a designated time interval (between 1
and 9 minutes) before an alarm will result
§ such linking may be appropriate for use with motion
detectors in “hostile” or “false-alarm prone”
environments
§ the ORBIT-Pro allows for 10 unique sets (pairs) of
zone links (pairs of zones) which can be manually-
specified, as required
a) from this display, press [ENTER] to reveal the first
zone link
b) from this display, press [ENTER] to modify the first
set (01) of zone links
c) as required, manually select the zone pairs by making
changes to the number of the first zone in the set,
followed by the number of the second zone
§ if necessary, use the UP-arrow (STAT) and/or
DOWN-arrow (BYP) keys to properly position the
cursor
§ zones “crossed with themselves” are not valid pairs
§ you may wish to establish a number of zone links,
but leave them deactivated at this time (see below)
d) press [ENTER] when completed, and select the
parameter governing the pairing, below:
Cross
Zoning
Pair Parameter:
§ chooses how the ORBIT-Pro will process violations of
paired zones
2 7 1 § None
3
§ use to temporarily disable any associated
zone pairings
2 7 2 § Ordered
§ use to effect an alarm if it’s desired that the first listed
zone be tripped before the second
2 7 3 § Not Ordered
§ use to effect an alarm in which either zone in the pair
may be tripped first
§ if so, the specified zone order (1
st
, 2
nd
) has no bearing
on the alarm activation
Time Slot: 1 min
§ choose a time interval between 1 and 9 minutes
defining the active internal
repeat the entire process, as required, for any additional zone links (up to 10) desired
INSTALLER PROG:
2)ZONES
SUBJECT: ZONES
7)CROSS ZONES ××
ZONE CROSSING:
01) 01 WITH 01 ××
CROSSING SET 01:
1ST=01 2ND=01