Installation and Programming Manual
62
ZONES: MISCELLANEOUS
Quick Key Item Default Explanation
2 0 MISCELLANEOUS
2 0 1 xx
+
E
N
T
E
R
Forced Arming
Not for UL
Installations
NO
§ allows the enabling or disabling of forced arming for
each of the system’s zones
§ forced arming, if enabled for a particular zone(s),
permits the system to be armed, even though such
zones may be faulted
§ if any zone(s) enabled for forced arming is faulted, the
keypad’s READY LED will blink during the disarmed
period
§ after the system is armed, all zones enabled for
forced arming will be bypassed at the conclusion of
the exit delay period
§ if a faulted zone–one enabled for forced arming–
becomes secured during the armed period–it will
become “unbypassed”, and be included among the
system’s armed zones
§ from this display:
a) press [ENTER], and at the resulting display,
b) arming will be enabled; press [ENTER]
c) use the UP-arrow or DOWN-arrow key to select
ENABLE or DISABLE, as it pertains to the
selected zone
d) press [ENTER]
e) repeat the above procedure for any zone(s) whose
forced armed status should be changed
f) when done, press the [TT] key, as required, to go
back to a different level of programming
g) if desired, codes reporting both the forced arming–
and the zone(s) bypassed in the process–will be
sent to the Central Station (see page 95 and 89,
respectively)
INSTALLER PROG:
2)ZONES
MISCELLANEOUS:
1)FORCED ARM
FORCED ARM:
ZONE#=01 (00:01)
FORCED ARM: 01
2)DISABLE